PT3 is a range of compact, configurable multiple-input transducers designed to meet the demanding needs of supply utilities and industrial applications. It offers accurate true-RMS measurements and quick response time. It is equipped with up to four load-independent, galvanically-isolated analogue outputs that can be configured on site for different input parameters, input range and output curves.

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Application

    • Data acquisition systems (SCADA)
    • Input to indication and monitoring applications
    • Process control
    • Plant automation
  • Key Feature

  • ▪      Best-in-class response time                              

    ▪      Long input range, site-configurable inputs, output and measurands

    ▪      Load-independent accuracy on all outputs

    ▪      4-in-1 programmable transducers

    ▪      Diagnostic LEDs

    ▪      Easy configuration through USB, without powering up the transducer 

    • Specification
    • Measurement functions (measurands)

      AC voltage

      Nominal input (Un)

      3 x 100 V to 415 V L-L (3-phase 3-wire system)

      3 x 57.5 V to 240 V L-N (3-phase 4-wire system)

      Measuring range

      0 to 130% of Un (up to 500 V)

      Measurement frequency

      50/60 Hz ± 5%

      Scale factor

      0.8 to 1.3 x Un (up to 500 V)

      Burden  

      ≤0.2 VA

      Maximum overload voltage

      1.3 x Un continuously

      2 x Un for 1 s, with up to 10 repetitions at 10 s intervals

      AC current

      Nominal input (In)

      1A to 5A

      Measuring current range

      0 to 150% of In

      Scale factor

      0.6 to 1.5

      Burden  

      ≤0.2 VA per phase

      Maximum overload current

      2 x In continuously

      20 x In for 1 s, with up to 10 repetitions at 100 s intervals

      Active power/reactive power

      Nominal input voltage (Un)

      3 x 100 V to 415 V L-L (3-phase 3-wire system)

      3 x 57.5 V to 240 V L-N (3-phase 4-wire system)

      Input voltage range

      0 to 130% of Un (up to 500 V)

      Nominal input current (In)

      1A to 5A

      Input current range

      0 to 150% of In

      Measurement frequency

      50/60 Hz ±5%

      Scale factor  

      0.5 to 1.5 (active power, at unity power factor)

      0.3 to 1 (reactive power, at reactive power factor >0.8 or unity)

      Un x In primary (apparent power)

      Power factor

      Nominal input voltage (Un)

      3 x 100 V to 415 V L-L (3-phase 3-wire system)

      3 x 57.5 V to 240 V L-N (3-phase 4-wire system)

      Input voltage range

      0 to 130% of Un (up to 500 V)

      Nominal input current (In

      1A to 5A

      Input current range

      0 to 150% of In

      Measurement frequency

      50/60 Hz ±5%

      Measurement range

      -1...0...1

      Accuracy

      ±0.2° (at nominal range)

      Auxiliary Supply

      High auxiliary

      Nominal voltage range

      80 V to 276 V AC/DC (±10%)

      Frequency

      50/60 Hz

      Maximum burden

      ≤11 VA, 6 W (with two outputs at 750 Ω each)

      ≤12 VA, 7 W (with four outputs at 750 Ω each)

      Low auxiliary

      Nominal voltage range

      24 V to 80 V DC (±10%)

      Maximum burden

      ≤6 W (with two outputs at 750 Ω)

      ≤8 W (with four outputs  at 750 Ω each)

      Analogue outputs

      Type

      Current & Voltage (bipolar)

      Maximum load resistance     

      ≤750 Ω for  20 mA, ≥2 kΩ for 10 V (for each output)  

      Response time

      5-cycle measurement (100 ms to 220 ms)

      Ripple

      <0.4 % peak to peak

      Temperature range

      Operating range

      -5 °C to +55 °C

      Functional range

      -20 °C to +70 °C

      Storage range

      -25 °C to +70 °C

      Mechanical

      Dimensions (W x H x D)

      45 mm x 75 mm x 105 mm

      Weight  

      0.7 kg (approx.)

      Material

      Fire-retardant polycarbonate (PC-FR), UL94 V-0

      Mounting

      DIN (EN 50022)

      Environmental

      Protection class   

      II (double insulation) EN 61010-1

      Pollution degree

      2

      Installation category

      CAT III for < 300V AC and CAT II for < 600V AC

      Protection degree

      Housing: IP 40; terminals: IP 20

      Compliance

      Standards

      IEC 60688, IEC 61010-1, IEC 61010-2-30, IEC 61326-1, DIN 50022

      Communications

      Mini-USB port

      For configuration (Can be configured without auxiliary power)

      RS-485

      Modbus-RTU enabled (suitable for integration with SCADA/PLC)

      Baud rate

      1200-38400 baud