Sprint 210
Sprint 210 three-phase meter provides flexibility through a modular design that readily accommodates the latest communications technologies utilising DLMS open protocol. The communications module can be factory installed, or fitted (or replaced) in the field. This enhances flexibility by enabling the use of ‘best of breed’ technologies, thereby future-proofing the utility’s investment.
Sprint 210 paves the way for easy and convenient data transfer from the meter to the utility’s back office and is the perfect solution for AMI applications. Provision for a range of communications technologies, including mesh radio, GPRS/3G devices and others, ensures that Sprint 210 will meet your current and future needs.
Application
- Domestic-three phase metering
- Small and medium commercial premises
- Advanced metering infrastructure (AMI) and non-AMI
- Suitable for co-generation metering applications
Key Feature
- Four-quadrant metering with import/export registration
- Multiple configurations function: up to 16 pre-loaded in the meter and executed in the field (variant specific)
- Support for AMI features: TOU based switching, boost, and remote firmware upgrades
- Large capacity power supply to support high communications device demands
- Modular communications ‘front belly’ design with support for a range of communication devices
- Remote de-energisation and energisation (direct and arm)
- Logging and remote notification (alarm) of events
- QoS (Quality of Supply) monitoring
- User-friendly tariff configurability features
- Enhanced load profile capability, with primary load profile for energy data and secondary load profile for supply quality
Benefits
- Modular communication for easy integration with AMI system
- Reduced on-site call times and cost
- Assists consumers in managing energy consumption
- Front-mounted communications module for easy access
- Specification
Electrical
Connection type
3-phase, 4-wire, active neutral, direct connected
Load terminals
Variant specific, (internal 31.5 A load control, 2 A load control)
Rated voltage (Vnom)
230 V AC, -20% to +15%
Maximum voltage
300 V (L-N) continuous
Impulse withstand
12 kV, 9 J, as per NMI M6
Frequency
50 Hz ±5%
Current range
10 A Ib, 100 A Imax
Accuracy
Class 1.0 (Active Energy), Class 2.0 (Reactive Energy)
Metrology Lamp
Two configurable metrological LEDs for active and reactive energy
Compliance
Standards
AS 62052.11, AS 62052.21, AS 62053.21, AS 62053.23, NMI-M6
IEC 62052.11, IEC 62052.21, IEC 62053.21, IEC 62053.23
Data storage capacity
Energy/demand load profile
1680 days (single channel) at 30-minute interval (configurable )
Configurable energy channels
Up to 8
Quality of Supply (QoS) parameters
3000 days (single parameter) at 30-minute interval (configurable) parameters include average voltage, current, THD, temperature etc.
Switches
Mains supply contactor
100 A
Auxiliary load control
31.5 A and/or 2 A (build option)
Mechanical
Dimensions (W x H x D)
180 mm x 252 mm x 118 mm (with 35 mm terminal block cover)
Enclosure
Flame-retardant polycarbonate
Sealing
Terminal cover, meter main cover, configuration button, communications module
Weight
2.4 kg (approx.)
Communications
Local
ANSI optical port (AS 62056.21)
Remote
LAN, HAN, WAN. Support for most communications topologies
Hot-swappable interchangeable modules, sealable separately
Pulse Output (option)
230 V AC, 2 A (volt free)
27 V DC, 27 mA (build option for up to 2 outputs)
Outage notification
Last gasp power supply (build option)
Environmental
Ingress protection
IP 53
Insulation class
Protective class II
Temperature
Operating: -10 °C to +60 °C
Storage: -25 °C to +70 °C
Humidity
95%, non-condensing