Specification
| Electrical | |
| Connection type | Direct connected |
| Wiring configuration | 3-phase 4-wire |
| Voltage range | 230/240 V (L-N) |
| Current range | 40-200 A |
| Accuracy | Class 1.0 |
| Mains frequency | 50 Hz ± 5% |
| Burden | Voltage circuit: < 1.0 W, 1.5 VA per phase |
| Insulation class | Protection class II |
| Impulse withstand | 10 kV |
| Compliance | |
| Standards | IS 13779, IEC 62052-11, IEC 62053-21, IEC 62053-23* |
| Mechanical | |
| Dimensions (W x H x D) | 365.0 X 283.0 X 221.0 mm (with extended terminal cover) |
| Weight | 4.5 kg (approx.) |
| Enclosure | Double-insulated glass-filled polycarbonate |
| Sealing | Provision for sealing screws |
| Terminals | Thread-through design suitable for current up to 200 A |