Specification
| Electrical | |
| Connection type | HV3/HV4 |
| Measurement voltage range | 57.7 V or 63.5 V (L-N) for HV4, 100 or 110 V (L-L) for HV3 |
| Measurement current range | Ib: 1A or 5A (configurable)*, Imax up to 10A (configurable)* |
| Frequency | 50 Hz ±5% |
| Burden with auxiliary/self (VT) powered | Current circuit: < 0.1 VA/phase @ 1A, < 0.5 VA/phase @ 5A Voltage circuit in case of Aux power: < 0.1 VA/phase Voltage circuit in case of internal/self power: < 6 VA/phase |
| Accuracy | Class 0.2S |
| Maximum overload Voltage | 1.5 times of nominal voltage continuously 2 times of nominal voltage for 0.5 second |
| Maximum overload current | 1.5 times of Imax continuously 10 times Imax for 1 second 20 times Imax for 0.5 second |
| Compliance | |
| Standards* | IS 14697 IS 15959 DLMS Indian companion standard, category B |
| Mechanical | |
| Dimensions (W x H x D) | 292mm x 201mm x 105mm (H x W x D) |
| Weight | 2 kg (+/- 200 gm) |
| Environmental | |
| Ingress protection | IP54 |
| Operating temperature | -10 °C to + 60 °C |
| Limit range of operation | -25 °C to + 70 °C |
| Storage temperature | -40 °C to + 80 °C |
| Temperature coefficient | <0.1%/10 C |