Product at a glance

Compact, long rangesite configurable transducers

PT3 is a range of compact, configurable multiple-input transducers designed to meet the demanding needs of supply utilities and industrial applications. It offers accurate true-RMS measurements and quick response time. It is equipped with up to four load-independent, galvanically-isolated analogue outputs that can be configured on site for different input parameters, input range and output curves.

Features

  • Best in class response time
  • Long range, site-configurable inputs, outputs and measurands
  • Load-independent accuracy on all outputs
  • 4-in-1 programmable transducers
  • Diagnostic LEDs
  • Compact footprint

Specification

Measurement functions (measurands)
AC voltage
Nominal input (Un) 3 x 100 V to 415 V L-L (3-phase 3-wire system)
3 x 57.5 V to 240 V L-N (3-phase 4-wire system)
Measuring range 0 to 130% of Un (up to 500 V)
Measurement frequency 50/60 Hz ± 5%
Scale factor 0.8 to 1.3 x Un (up to 500 V)
Burden ≤0.2 VA
Maximum overload voltage 1.3 x Un continuously
2 x Un for 1 s, with up to 10 repetitions at 10 s intervals
AC current
Nominal input (In) 1A to 5A
Measuring current range 0 to 150% of In
Scale factor 0.6 to 1.5
Burden ≤0.2 VA per phase
Maximum overload current 2 x In continuously
20 x In for 1 s, with up to 10 repetitions at 100 s intervals
Active power/reactive power/ apparent power
Nominal input voltage (Un) 3 x 100 V to 415 V L-L (3-phase 3-wire system)
3 x 57.5 V to 240 V L-N (3-phase 4-wire system)
Input voltage range 0 to 130% of Un (up to 500 V)
Nominal input current (In) 1A to 5A
Input current range 0 to 150% of In
Measurement frequency 50/60 Hz ±5%
Scale factor 0.5 to 1.5 (active power, at unity power factor)
0.3 to 1 (reactive power, at reactive power factor >0.8 or unity)
Un x In primary (apparent power)
Active power factor / load power factor
Nominal input voltage (Un) 3 x 100 V to 415 V L-L (3-phase 3-wire system)
3 x 57.5 V to 240 V L-N (3-phase 4-wire system)
Input voltage range 0 to 130% of Un (up to 500 V)
Nominal input current (In) 1A to 5A
Input current range 0 to 150% of In
Measurement frequency 50/60 Hz ±5%
Measurement range -1…0…1
Accuracy ±0.2° (at nominal range)
For more details click here.