Specification
Electrical | |
Connection type | HV3/HV4 |
Measurement voltage range | 57.7 V or 63.5 V (L-N) for HV4, 100 or 110 V (L-L) for HV3 |
Measurement current range | Ib: 1A or 5A (configurable)*, Imax up to 10A (configurable)* |
Frequency | 50 Hz ±5% |
Accuracy | Class 0.2S |
Maximum overload Voltage | 1.5 times of nominal voltage continuously 2 times of nominal voltage for 0.5 second |
Maximum overload current | 1.5 times of Imax continuously 10 times Imax for 1 second 20 times Imax for 0.5 second |
Compliance | |
Standards* | IS 14697 IS 15959 DLMS Indian companion standard, category B |
Mechanical | |
Dimensions (W x H x D) | 292mm x 201mm x 105mm (H x W x D) |
Weight | 2 kg (+/- 200 gm) |
Environmental | |
Ingress protection | IP54 |
Operating temperature | -10 °C to + 60 °C |
Limit range of operation | -25 °C to + 70 °C |
Storage temperature | -40 °C to + 80 °C |
Temperature coefficient | <0.1%/10 C |