Specification
| Electrical | |
| Connection type | 1 Phase, 2 wires, active-neutral, direct connected |
| Measuring elements | 1 or 2 elements |
| Rated voltage | 230 V AC, -20% to +15% |
| Maximum voltage | 300 V (L-N) continuous |
| Impulse withstand | 10 kV, 0.5Joule (as per IEC) | 12 kV, 9Joule (as per NMI M6) |
| Current range | 10 A Ib, 100 A Imax |
| Accuracy | Class 1.0 (active energy), class 2.0 (reactive energy) |
| Metrology lamp | Two metrological LEDs for active and reactive energy (configurable pulse rate) |
| Compliance | |
| Standards* | AS 62052.11, AS 62052.21, AS 62053.21, AS 62053.23, NMI M6-1 IEC 62052.11, IEC 62052.21, IEC 62053.21, IEC 62053.23, IEC62056 series (DLMS/COSEM) Exceeds minimum services specification, as per the Australian National Electricity Amendment (expanding competition in metering and related services) |
| Mechanical | |
| Dimensions (W x H x D) | 145mm x 190mm x 112mm (standard terminal block cover) 145mm x 230mm x 112mm (extended terminal block cover) |
| Enclosure | Fire-retardant polycarbonate |
| Sealing | Terminal cover, meter main cover, config button, communication module |
| Weight | 1.4 to 1.6 kg (approx) depending on variant |
| Display | 7-character alphanumeric LCD with backlight and icons for status |