Specification
Electrical | |
Connection type | 3 phase, 4 wire, direct connected |
Rated voltage | 230 V AC, -20% tp +15% |
Maximum voltage | 460 V (L-N) |
Impulse withstand | 10 kV, 0.5J (as per IEC) 12 kV, 9J (as per NMI M6) |
Frequency | 50 Hz ± 5% |
Current range | 10 A Lb, 100A Imax |
Accuracy | Class 1.0 (active energy), class 2.0(reactive energy) |
Compliance | |
Standards* | AS 62052.11, AS 62052.21, AS 62053.21, AS 62053.23, NMI M6-1 IEC 62052.11, IEC 62052.21, IEC 62053.21, IEC 62053.23, IEC62056 series (DLMS/COSEM) Exceeds minimum services specification, as per the Australian National Electricity Amendment (expanding competition in metering and related services) |
Mechanical | |
Dimensions (WxHxD) | 180 mm x 221 mm x 118 mm (standard terminal block cover) 180 mm x 252 mm x 118 mm (extended terminal block cover) |
Enclosure material | Flame-retardant polycarbonate |
Sealing | Terminal cover, meter main cover, config button, communications module |
Weight | 2.4 kg (approx.) |
Display | 8-character alphanumeric LCD with backlight and icons for status |
Environmental | |
Temperature | Operating: -10°C to +60°C | Storage: -25°C to +70°C |
Humidity | 95%, non-condensing |
Ingress protection | IP 53 |
Insulation class | Protective class II |