Specification
| Electrical | |
| Connection type | 3-phase 4-wires, direct connected | 
| Rated voltage | 230 V AC, -20% to +15% | 
| Maximum voltage | 460V (L-N) continuous | 
| Impulse withstand | 12 kV, 9 J, as per NMI M6 | 
| Frequency | 50 Hz ±5% | 
| Current range | 10-100A | 
| Frequency | 50 Hz ±5% | 
| Accuracy class | Class 1.0 (active energy), Class 2.0 (reactive energy) | 
| Metrology Lamp | Two configurable metrological LEDs for active and reactive energy | 
| Compliance | |
| Standards | NMI M6-1, AS 62052.11, AS 62053.21, AS 62053.23, AS 62052.21Exceeds minimum services specification as per the National Electricity Amendment (expanding competition in metering and related services. Rule 2015 No. 12) | 
| Data storage capacity | |
| Energy/demand load profile | 395 days (per channel) at 30-minute interval (configurable), up to 4 channels, 65 days (per channel) at 5-minute interval (configurable), up to 4 channels  | 
| Quality of Supply (QoS) parameters | 90 days (per parameter) at 30-minute interval (configurable), up to 8 parameters, including average voltage, current, phase angles, temperature | 
| Switches/outputs | |
| Mains supply contactor | 100 A | 
| Auxiliary load control | 31.5A, variant specific | 
| Mechanical | |
| Dimensions (W x H x D) | 180 mm x 252 mm x 118 mm | 
| Enclosure material | Flame retardant poly-carbonate | 
| Weight | 2.4 kg (approx.) | 
| Sealing provisions | Terminal cover, meter main cover, communications module | 
| Display | 8-character alphanumeric LCD with backlight and icons for status | 

											
											
											
											